Visita Virtual de 360° a la Subestación Aniversario de Edenor
Virtual Tour of Subestación Aniversario
Introduction to the Visit
- The visit will explore the Subestación Aniversario with eight stops, featuring videos by Engineer Marcelo Fabbro, who oversees operations and substation supervision.
- The activity lasts approximately one hour and is self-guided; questions are encouraged throughout the tour rather than at the end.
- Participants can access a link for further exploration of this virtual experience, allowing repeated visits and use in educational settings.
Overview of Subestación Aniversario
- Located in Vicente López, just 600 meters from Río de la Plata and 800 meters from Avenida General Paz, designed to blend with its environment resembling a ship.
- This year’s virtual experience allows broader access; over 1,000 people have participated across multiple presentations.
Safety Protocols
- Normally, visitors must wear helmets and protective shoes when entering the substation; however, these requirements are waived for the virtual tour.
Understanding Electricity
Importance of Electricity
- Electricity is essential for daily activities such as lighting, refrigeration, charging devices, and internet usage.
- Proper generation and distribution of electricity are crucial for homes and businesses; substations play a key role in this process.
Role of Substations
- Substations transform high-voltage electricity into lower voltages suitable for distribution to consumers.
Features of Subestación Aniversario
Construction Details
- Inaugurated in 2017 to commemorate Edenor's 25th anniversary; built on a uniquely narrow plot measuring 125m long by 25m wide.
- The construction faced challenges due to space constraints requiring innovative engineering solutions.
Investment Impact
- The investment totaled $12.6 million benefiting around 75,000 customers in Vicente López and northern Buenos Aires.
Types of Substations
Classification by Functionality
- There are elevating substations near power plants that increase voltage for transport and reducing substations that decrease voltage for safe distribution.
Technological Advancements
- New technologies allow compact designs occupying only 4% to 8% of conventional sizes while maintaining operational efficiency.
Control Room Insights
Control Room Overview
- All substations include control rooms where electrical components are monitored; this room houses telecontrol systems ensuring operational safety.
Auxiliary Services Explained
- Auxiliary services provide necessary energy for equipment operation within the substation including lighting and ventilation systems.
Maneuvering Area Operations
Maneuvering Area Description
- The maneuvering area contains outdoor equipment operating at two voltage levels: primary (132 kV), linked to transmission systems, and secondary (13.2 kV), connected to distribution networks.
High Voltage Equipment
High Voltage Components
- Equipment includes high-voltage disconnect switches which separate parts electrically providing visible cuts during maintenance operations.
Conclusion on Equipment Functionality
- Interruptors monitor continuously ensuring rapid response during faults generating alarms locally or sending alerts back to control centers.
Overview of Substation Platforms
Structure and Functionality
- The platforms are constructed from concrete to support transformers and manage oil spills during emergencies.
- They include a flame wall, which must exceed 2 meters in height to prevent fire spread between transformers, allowing firefighters to cool adjacent units safely.
- The functionality of all components within the substation is critical for operational safety and efficiency.
Mixed-Type Substations
Transmission and Distribution
- This mixed-type substation facilitates both transmission from other substations (Edison and Nuevo Puerto) and distribution through its transformers.
- Transformers are standardized at 80 MVA, with configurations allowing simultaneous transmission and power extraction.
Transformer Configuration
Technical Specifications
- Each transformer has a primary and secondary output, providing two outputs of 40 MVA each through medium voltage cables.
- These transformers do not utilize tertiary windings; however, they are used in higher voltage applications (120 kV).
Control Room Insights
Energy Distribution Management
- The control room houses maneuvering panels that distribute energy among nearby transformation centers using four sections with eight outgoing cables each.
- An automatic load transfer system ensures continuity during failures by closing couplers under specific conditions.
Safety Features in Equipment
Protection Mechanisms
- Increased safety measures protect active parts from arc flash incidents, minimizing risks for operators and surrounding equipment.
- Primary distribution cells feature removable switches for quick maintenance without compromising operational flexibility.
Medium Voltage Switches
Operational Characteristics
- Medium voltage switches use vacuum-sealed contacts to interrupt nominal currents or short circuits effectively while operating up to 17.5 kV.
- Interchangeability allows rapid replacement of faulty switches with similar models.
Synchronization Queries
System Integration
- Normal operations involve synchronization within the same subsystem for effective coupling; this is managed by dispatch based on demand conditions.
Relay Protection Systems
Advanced Monitoring
- Modern relays function as small computers monitoring outputs; they coordinate protection mechanisms across multiple levels within the system.
Capacitor Banks
Reactive Power Management
- Capacitor banks installed at the substation regulate reactive power flow between sources and loads while ensuring personnel safety against direct contact.
Site Selection Challenges
Practical Considerations
- Selecting sites for new substations involves balancing theoretical planning against real-world constraints like land availability or existing structures.
Future Expansion Plans
Anticipated Developments
- Edenor plans future substations including José y Sepas, Libertad in Merlo, San Juan near Campos de Mayo, aiming to meet increasing demand efficiently.