Elektrická instalace - Instalace uzemnění do základů rodinného domu.

Elektrická instalace - Instalace uzemnění do základů rodinného domu.

Grounding Installation for a Family House

Overview of Grounding Materials and Tools

  • The project involves laying down grounding for a family house, requiring specific materials such as grounding straps, connectors, and corrosion protection.
  • Essential tools include a hammer for driving supports, a wrench for connections, and a flex tool for cutting metal components. Additional tools like a shovel may be needed to adjust the ground.

Steps in Grounding Installation

  • Supports are placed around the perimeter of the excavation site with grounding straps attached to them. A complete circuit is created using metal strips at each corner connected to vertical rods (cylinders) for lightning protection. One additional rod is extended into the technical room for main grounding connection.
  • Supports are positioned one meter from the edge of the excavation to allow space for two connectors leading to the lightning rod output while maintaining 15 cm above ground level for stability. A string is used to ensure even height across all supports.

Adjustments and Measurements

  • Initial spacing between supports was calculated at 1.40 m but adjusted to 120 cm based on practical considerations regarding soil conditions and structural integrity concerns. Shorter distances were also noted at 110 cm where necessary adjustments were made during installation.
  • It’s crucial that metal strips are fully encased in concrete; improper placement can lead to voids beneath them which could compromise their effectiveness over time due to inadequate concrete coverage around them. This ensures proper bonding with surrounding material during curing processes.

Finalizing Connections

  • After securing all supports, attention turns towards ensuring that connections between different sections are properly insulated against corrosion using protective materials like Gumosvalt or anti-corrosion tape (Antikorplast). These materials help maintain integrity where transitions occur between different substrates (e.g., concrete to soil).
  • Five connections have been completed using tape insulation; if any issues arise with these joints, further taping will be applied as needed based on performance observations during installation phases. Proper sealing is essential in preventing moisture ingress which could lead to deterioration over time.

Conclusion of Installation Process

  • The overall setup appears stable after initial assessments; however, ongoing monitoring will be necessary post-installation to ensure that no shifting occurs under load from surrounding earth or water accumulation which might affect support structures negatively over time as they settle into place naturally through environmental factors like rain or frost heave effects on soil composition nearby foundations areas being worked upon currently here today!
Video description

Ukázka práce